Manufacturer:: Amphenol
Amphenol Telaire T6615 Dual Channel NDIR Carbon Dioxide Sensor Module
The Dual Channel Module is a compact CO2 sensor module designed to integrate into existing controls and equipment. It is engineered to meet the volume, cost, and delivery expectations of Original Equipment Manufacturers (OEMs).
| Parameter | Value |
| Method | Dual-channel Non Dispersive Infrared (NDIR), gold plated 0.38 in (9.65 mm) optics, diffusion or flow through sampling |
| Measurement Range | 0 to 2000 ppm, 0 to 5000 ppm, 0 to 10,000 ppm, 0 to 50,000 ppm |
| Dimensions | 2.25 in X 1.365 in X 0.60 in (57.15 mm X 34.67 mm X 15.24 mm) |
| Accuracy | 75 ppm or 10% of reading (whichever is greater) |
| Digital Output | UART @ 19200 Baud |
| Analog Output | 0 to 4 VDC |
| Temperature Dependence | 0.2% FS per °C |
| Pressure Dependence | 0.135% of reading per mm Hg |
| Power Supply Requirements | 5 VDC regulated (±5%) |
| Power Consumption | 0.90 watts peak, 0.165 watts average |
| Response Time | < 2 minutes for 90% step change typical |
| Warm Up Time | < 2 minutes (operational), 10 minutes (maximum accuracy) |
| Interface Connections | Designed for 12 pin male header with 0.1 in (2.54 mm) spacing. Header not included. |
| Operating Conditions | 32°F to 122°F (0°C to 50°C), 0 to 95% RH, non condensing |
| Storage Conditions | -40°F to 158°F (-40°C to 60°C), non condensing |
| Flow Rates (Via Flow Ports) | Flow through version: 50 cc/min maximum, Diffusion version: 80 - 120 cc/min |
| Warranty Terms | 12 months |