Manufacturer:: Shenzhen Senseiot
SENSEIOT ZX706S‑DCS Wall‑Mounted IAQ Comprehensive Air Quality Transmitter Module
The ZX706S-DCS is a multi-parameter online atmospheric environment detector designed for monitoring indoor environments and public open areas. It measures PM2.5 particle concentration, temperature, humidity, air pressure, VOC, CO2, O2, formaldehyde, carbon monoxide, and other parameters. The device offers powerful functionality in a compact form factor.
| Operating temperature | -10 ~ 50℃ |
| Operating humidity | 0 ~ 95%RH |
| Storage temperature | -20 ~ 60℃ |
| Power input | DC 12~24V |
| Current consumption | Average 350mA, peak 600mA |
| Signal output | Modbus RS485, 9600bps, 1 start bit, 8 data bits, 1 stop bit, no parity (optional WiFi, ZIGBEE, TCP/IP) |
| Size | 450g / 133mm x 133mm x 39mm |
| PM2.5 detection range | 0~1000µg/m3 |
| PM2.5 accuracy | ±15µg/m3 or 10% of value |
| PM2.5 test method | Optical scattering |
| HCHO detection range | 0~5.00ppm |
| HCHO accuracy | ±5% FS |
| HCHO test method | Electrochemistry |
| CO detection range | 0~500ppm |
| CO accuracy | ±5% FS |
| CO test method | Electrochemistry |
| VOC detection range | 0~10mg/m3 |
| VOC accuracy | ±8% FS |
| VOC test method | Semiconductor |
| Smoke detection range | 0~2000ppm |
| Smoke test method | Semiconductor |
| O2 detection range | 0~25.0%VOL |
| O2 accuracy | ±2% FS |
| O2 test method | Electrochemistry, 2 years life |
| CO2 detection range | 0~5000ppm |
| CO2 accuracy | ±50ppm or ±5% of value |
| CO2 test method | Nondispersive infrared detection |
| Temperature detection range | -20 ~ 85℃ |
| Temperature accuracy | ±0.5℃ |
| Humidity detection range | 0 ~ 100%RH |
| Humidity accuracy | ±3%RH |
| Pressure detection range | 200~1200hPa |
| Pressure accuracy | ±0.1% |
| Noise detection range | 30-130DB |
| Noise accuracy | ±1.5DB |
| Noise test method | Electret |
| Illumination detection range | 0-65535LUX |
| Illumination accuracy | ±5% |
| Illumination test method | Photoelectric principle |
| Extendable sensors | Up to 4 electrochemical sensors for NO, O3, NO2, SO2, H2S, NH3, VOC, PH3, CL2, HCL, HCN, HF (parameters depend on selected sensors) |
To learn more, please download the PDF.